Specifications:
- Manufacturer Phoenix Contact
- Part Number 2725260
- Utilization restriction EMC: class A product, see manufacturer's declaration in the download area
- Width 168 mm
- Height 107 mm
- Depth 20 mm
- Degree of protection IP00
- Ambient temperature (operation) 0 °C ... 55 °C (acc. to EN 60204-1)
- Ambient temperature (storage/transport) -25 °C ... 75 °C (acc. to EN 60204-1)
- Permissible humidity (operation) 75 % (on average, 85% infrequently, non-condensing)
- Air pressure (operation) 860 hPa ... 1080 hPa (up to 2000 m above mean sea level)
- Air pressure (storage/transport) 660 hPa ... 1080 hPa (up to 3000 m above sea level)
- Control system IBM-compatible PCs with PCI slot
- Diagnostics tool DIAG+ from version 1.0x
- Configuration tool CMD from version 4.5x
- Operating system Windows NT
- Operating system Windows 2000
- Operating system Windows XP
- Operating system Windows 7
- Operating system Venturcom RTX 5.x
- Operating system Further types on request
- Driver Windows NT
- Driver Windows 2000
- Driver Windows XP
- Driver Windows 7
- Driver Venturcom RTX 5.x
- Driver Further types on request
- Application interface HFI
- Application interface DDI
- Configuration tool CMD from version 4.5x
- Configuration tool Config+ from version 1.00 onwards
- Diagnostics tool DIAG+ from version 1.0x
- Power supply connection Via PCI bus
- Typical current consumption 0.7 A
- Supply Voltage 5 V DC
- Supply voltage range ± 5 % (including ripple)
- Power dissipation max. 3.5 W
- Weight 126.1 g
- Format Short plug-in card, 1-slot
- Interface INTERBUS remote bus
- Connection Method 9-pos. D-SUB female connector, with electrical isolation
- Interface Parameterization/operation/diagnostics
- Connection Method RS-232-C, Mini-DIN female
- Interface Host system
- Connection Method PCI bus, 32 bit, 33 MHz, 5 V
- Interface Direct I/Os
- Connection Method 14-pos. FLK pin strip
- Interrupts 1 IRQ, PnP
- Input name Digital inputs
- Number of inputs 6 (EN 61131-2 type 1)
- Connection technology FLK cable connector (14-pos.)
- Nominal input voltage U<sub>IN</sub> 24 V DC
- Output name Digital outputs
- Number of outputs 2
- Connection technology FLK cable connector (14-pos.)
- Maximum output current per channel 0.5 A
- Amount of process data max. 8192 Bit (INTERBUS-Master)
- Number of supported devices max. 512 (of which 254 are remote bus devices/bus segments)
- Number of devices with parameter channel max. 126
- Connection in acc. with standard CUL
- China RoHS Environmentally Friendly Use Period = 50
- China RoHS For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”
- Nominal input voltage U<sub>IN</sub> 24 V DC
- REACh SVHC Lead 7439-92-1
- Transmission speed 500 kbps
- Transmission speed 500 kbps500 kbps 2 Mbps